CCTS-2Т-5SM6

CCTS 6, 10 or 20/ 0.4 kV 2 x 1000 KvA with a cable inlet and cable outlets, terminal and intermediary type, housed in a concrete- prefab body.
Technical Details
  MV two cable inputs and one output to the transformer. The inputs are equipped with Switch modular unit type IM (see SM6 range of Merlin Gerin) The transformer protection is equipped with Fuse-Switch combination modular unit type QM. There is a posibility of energy measuring in MV section using GBC-B modular unit. All modular units are metal-enclosed, using sulphur hexafluoride for insulation. The servicing of the CCTS can be one-sided, two-sided or three-sided on customers request.

  Rated voltage of MV section: 12 or 24 kV
  Rated voltage of LV section: 0,4 kV
  Rated short-time withstand current: 20kA/1s
  Rated peak withstand current: 50 kA max
  Protection degree: IP 33 or IP 43
  Possibility of energy measuring in MV section
  LV section: type of equipment and number of feeders- according to customer`s requirements
Conditions of Service Use
Ambient temperature range: 40 °C to + 45 °C
Relative humidity:100% rain
Altitude:Up to 1000 м.
Environment: absence of current-conductive gases, vapours and dust, fire-proof and explosion-proof surroundings

Principle Electric Diagram CCTS 2T-4SM6 2 x 1000 kVA 20(10)/0.4 kV


Drawing of Dimensions CCTS 2T-4SM6 2 x 1000 kVA 20(10)/0.4 kV