CCTS-P-1T4K

CCTS 6, 10 or 20/ 0.4 kV up to 1000 KvA with a cable inlet and cable outlets, terminal or intermediary type, housed in a concrete-prefab body.
Technical Details
  MV two cable inputs and one output to the transformer. The inputs are equipped with Switch-Disconnectors having Earthing Switch. The transformer protection is realized by Switch-Disconnectors combined with MV fuses. The current transformers are mounted below the MV fuses. The voltage transformers are in separate cell and are protected by Switch-Disconnectors combined with MV fuses. The servicing of the CCTS can be one-sided, two-sided or three-sided on customers request.

  Rated voltage of MV section: 12 or 24 kV
  Rated voltage of LV section: 0,4 kV
  Rated short-time withstand current: 20kA/1s
  Rated peak withstand current: 50 kA max
  Protection degree: IP 33 or IP 43
  Possibility of energy measuring in MV section
  LV section: type of equipment and number of feeders- according to customer`s requirements
Conditions of Service Use
Ambient temperature range: 40 °C to + 45 °C
Relative humidity:100% rain
Altitude:up to 1000 м.
Environment:absence of current-conductive gases, vapours and dust, fire-proof and explosion-proof surroundings

Principle Electric Diagram CCTS 1Т-4К до 630 kVA 20(10)/0.4 kV


Drawing of Dimensions CCTS 1Т-4К до 630 kVA 20(10)/0.4 kV